Chapter 11 - Refrigeration Cycles - Problems - Page 642: 11-36C

Answer

See explanation below.

Work Step by Step

The minimum pressure that the refrigerant needs to be compressed to is the saturation pressure of the refrigerant at 30°C, which is 770.64 kPa. Below this pressures, the refrigerant will condense at temperature lower than ambient temperature, which is not possible.